Pad Mounted Transformers
Manufactured in India. Designed for the World.
Pad mounted transformers are compact, ground-mounted electrical transformers designed for safe and reliable power distribution in utility, industrial, commercial and infrastructure applications. KLR Transformers is a pad mounted transformer manufacturer and supplier offering transformers designed for dependable operation, efficient power distribution and long service life. Available up to 10 MVA and 34.6 kV, each transformer is engineered according to individual system requirements and manufactured to applicable ANSI and IEEE standards. With robust construction, appropriate cooling arrangements and application-specific designs, our pad mounted transformers provide reliable solutions for modern power distribution networks.

Pad Mounted Transformer Technical Specifications
| Parameter | Specification |
|---|---|
| Capacity range | 100 kVA to 10000 kVA |
| Voltage class | Up to 38.5 kV |
| Insulation system | Class A & Class B Oil-Impregnated Paper |
| Cooling | ONAN / ONAF / KNAN / KNAF |
| Enclosure type | Tamper-Resistant, Dead-Front or Live-Front Pad Mounted Construction |
| Tank construction | Welded Sealed Tank or Bolted with Tamper-Proof Compartments |
| Standards | ANSI, IEEE, CSA, UL, and DOE |
| Winding material | Electrolytic Grade Copper or Aluminium |
| Winding type | Foil / Disc / Helical / Layer |
| Temperature rise | Up to 65°C |
| Vector group | Dyn11 / YNd1 / Other Vector Groups on Request |
| Insulation levels (BIL) | Up to 200 kVp (As per Voltage Class) |
| Tapping range | DETC |
| Frequency | 50 Hz / 60 Hz |
| Testing | Complete Routine Tests as per IS, IEC, ANSI, IEEE. Type Tests on request. |
Optional Features
- Dead-Front or Live-Front Construction
- Loop Feed or Radial Feed Configuration
- Bay-O-Net and Current Limiting Fuse Protection
- Load Break Switch (2-Way / 4-Way)
- SCADA / Remote Monitoring Compatibility
- Liquid Temperature Indicator (OTI)
- Winding Temperature Indicator (WTI)
- Pressure Relief Device (PRD)
- Anti-Corrosive Paint System for Coastal Environments C4/C5
- FR3 Natural Ester Fluid, Synthetic Ester Fluid & ASTM
- Tamper-Proof Locking System
Enquire About Pad Mounting Transformer Supply.
Share your project location, kVA rating, primary voltage, configuration (loop or radial), and timeline. We will provide a specification and export quote within 2 business days.